    CVE-2024-10313 (GCVE-0-2024-10313)

    Vulnerability from nvd – Published: 2024-10-24 17:41 – Updated: 2024-10-24 18:29
    VLAI
    Title
    iniNet Solutions SpiderControl SCADA PC HMI Editor Path Traversal
    Summary
    iniNet Solutions SpiderControl SCADA PC HMI Editor has a path traversal vulnerability. When the software loads a malicious ‘ems' project template file constructed by an attacker, it can write files to arbitrary directories. This can lead to overwriting system files, causing system paralysis, or writing to startup items, resulting in remote control.
    SSVC
    Exploitation: none Automatable: no Technical Impact: total
    CISA Coordinator · CISA-ADP (v2.0.3)
    Decision recorded 2024-10-24 18:23 UTC
    CWE
    Impacted products
    Vendor Product Version
    iniNet Solutions SpiderControl SCADA PC HMI Editor Affected: 8.10.00.00
    Create a notification for this product.
    spidercontrol scada_pc_hmi_editor Affected: 8.10.00.00
        cpe:2.3:a:spidercontrol:scada_pc_hmi_editor:*:*:*:*:*:*:*:*
    Create a notification for this product.
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "affected": [
              {
                "cpes": [
                  "cpe:2.3:a:spidercontrol:scada_pc_hmi_editor:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unaffected",
                "product": "scada_pc_hmi_editor",
                "vendor": "spidercontrol",
                "versions": [
                  {
                    "status": "affected",
                    "version": "8.10.00.00"
                  }
                ]
              }
            ],
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2024-10313",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-10-24T18:23:13.626806Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-10-24T18:29:45.979Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "SpiderControl SCADA PC HMI Editor",
              "vendor": "iniNet Solutions",
              "versions": [
                {
                  "status": "affected",
                  "version": "8.10.00.00"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "finder",
              "value": "elcazator from ELEX FEIGONG RESEARCH INSTITUTE of Elex CyberSecurity, Inc. reported this vulnerability to CISA."
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "iniNet Solutions SpiderControl SCADA PC HMI Editor has a path traversal \nvulnerability. When the software loads a malicious \u2018ems\u0027 project \ntemplate file constructed by an attacker, it can write files to \narbitrary directories. This can lead to overwriting system files, \ncausing system paralysis, or writing to startup items, resulting in \nremote control."
                }
              ],
              "value": "iniNet Solutions SpiderControl SCADA PC HMI Editor has a path traversal \nvulnerability. When the software loads a malicious \u2018ems\u0027 project \ntemplate file constructed by an attacker, it can write files to \narbitrary directories. This can lead to overwriting system files, \ncausing system paralysis, or writing to startup items, resulting in \nremote control."
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 8,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "HIGH",
                "integrityImpact": "HIGH",
                "privilegesRequired": "LOW",
                "scope": "UNCHANGED",
                "userInteraction": "REQUIRED",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H",
                "version": "3.1"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            },
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 8.6,
                "baseSeverity": "HIGH",
                "privilegesRequired": "LOW",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "PASSIVE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "HIGH",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-22",
                  "description": "CWE-22 Path Traversal",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2024-10-24T17:41:56.069Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-298-02"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "iniNet Solutions recommends that users update SpiderControl SCADA PC HMI Editor to version \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://spidercontrol.net/download/download-area-2/?lang=en#editor\"\u003e8.24.00.00\u003c/a\u003e to mitigate this vulnerability.\n\n\u003cbr\u003e"
                }
              ],
              "value": "iniNet Solutions recommends that users update SpiderControl SCADA PC HMI Editor to version  8.24.00.00 https://spidercontrol.net/download/download-area-2/  to mitigate this vulnerability."
            }
          ],
          "source": {
            "advisory": "ICSA-24-298-02",
            "discovery": "EXTERNAL"
          },
          "title": "iniNet Solutions SpiderControl SCADA PC HMI Editor Path Traversal",
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2024-10313",
        "datePublished": "2024-10-24T17:41:56.069Z",
        "dateReserved": "2024-10-23T18:25:15.297Z",
        "dateUpdated": "2024-10-24T18:29:45.979Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2024-8232 (GCVE-0-2024-8232)

    Vulnerability from nvd – Published: 2024-09-10 19:44 – Updated: 2024-09-12 13:36
    VLAI
    Title
    iniNet Solutions SpiderControl SCADA Web Server Unrestricted Upload of File with Dangerous Type
    Summary
    SpiderControl SCADA Web Server has a vulnerability that could allow an attacker to upload specially crafted malicious files without authentication.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: partial
    CISA Coordinator · CISA-ADP (v2.0.3)
    Decision recorded 2024-09-12 13:34 UTC
    CWE
    • CWE-434 - Unrestricted Upload of File with Dangerous Type
    Impacted products
    Vendor Product Version
    iniNet Solutions GmbH SpiderControl SCADA Web Server Affected: 0 , ≤ v2.09 (custom)
    Create a notification for this product.
    spidercontrol scada_webserver Affected: 0 , ≤ 2.09 (custom)
        cpe:2.3:a:spidercontrol:scada_webserver:*:*:*:*:*:*:*:*
    Create a notification for this product.
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "affected": [
              {
                "cpes": [
                  "cpe:2.3:a:spidercontrol:scada_webserver:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unaffected",
                "product": "scada_webserver",
                "vendor": "spidercontrol",
                "versions": [
                  {
                    "lessThanOrEqual": "2.09",
                    "status": "affected",
                    "version": "0",
                    "versionType": "custom"
                  }
                ]
              }
            ],
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2024-8232",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-09-12T13:34:02.939872Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-09-12T13:36:10.295Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "SpiderControl SCADA Web Server",
              "vendor": "iniNet Solutions GmbH",
              "versions": [
                {
                  "lessThanOrEqual": "v2.09",
                  "status": "affected",
                  "version": "0",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "finder",
              "value": "elcazators ELEX FEIGONG RESEARCH INSTITUTE of Elex CyberSecurity, Inc reported this vulnerability to CERT/CC."
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "SpiderControl SCADA Web Server has a vulnerability that could allow an \nattacker to upload specially crafted malicious files without \nauthentication."
                }
              ],
              "value": "SpiderControl SCADA Web Server has a vulnerability that could allow an \nattacker to upload specially crafted malicious files without \nauthentication."
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "NONE",
                "baseScore": 7.5,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "HIGH",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
                "version": "3.1"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            },
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 8.7,
                "baseSeverity": "HIGH",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "NONE",
                "vulnConfidentialityImpact": "NONE",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-434",
                  "description": "CWE-434 Unrestricted Upload of File with Dangerous Type",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2024-09-10T19:44:18.096Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-254-02"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "IniNet Solutions has released a new version of SpiderControl SCADA \nServer, (3.2.2), to address this issue. It can be found at the following\n location: \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://spidercontrol.net/download/download-area-2/?lang=en\"\u003ehttps://spidercontrol.net/download/download-area-2/?lang=en\u003c/a\u003e\n\n\u003cbr\u003e"
                }
              ],
              "value": "IniNet Solutions has released a new version of SpiderControl SCADA \nServer, (3.2.2), to address this issue. It can be found at the following\n location:  https://spidercontrol.net/download/download-area-2/?lang=en"
            }
          ],
          "source": {
            "advisory": "ICSA-24-254-02",
            "discovery": "EXTERNAL"
          },
          "title": "iniNet Solutions SpiderControl SCADA Web Server Unrestricted Upload of File with Dangerous Type",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "IniNet Solutions reminds users that the webserver is designed to be used\n in a protected environment. IniNet Solutions GmbH recommends that users\n never connect control system software directly to the Internet. If a \nuser must connect to the Internet, IniNet Solutions GmbH recommends \nusing a managed infrastructure to do so.\n\n\u003cbr\u003e"
                }
              ],
              "value": "IniNet Solutions reminds users that the webserver is designed to be used\n in a protected environment. IniNet Solutions GmbH recommends that users\n never connect control system software directly to the Internet. If a \nuser must connect to the Internet, IniNet Solutions GmbH recommends \nusing a managed infrastructure to do so."
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2024-8232",
        "datePublished": "2024-09-10T19:44:18.096Z",
        "dateReserved": "2024-08-27T13:40:41.730Z",
        "dateUpdated": "2024-09-12T13:36:10.295Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2023-3329 (GCVE-0-2023-3329)

    Vulnerability from nvd – Published: 2023-08-02 22:26 – Updated: 2024-10-29 17:48
    VLAI
    Title
    CVE-2023-3329
    Summary
    SpiderControl SCADA Webserver versions 2.08 and prior are vulnerable to path traversal. An attacker with administrative privileges could overwrite files on the webserver using the HMI's upload file feature. This could create size zero files anywhere on the webserver, potentially overwriting system files and creating a denial-of-service condition.
    Severity
    No CVSS data available.
    SSVC
    Exploitation: none Automatable: no Technical Impact: total
    CISA Coordinator · CISA-ADP (v2.0.3)
    Decision recorded 2024-10-29 17:48 UTC
    CWE
    Impacted products
    Vendor Product Version
    iniNet SCADAWebServer Affected: 0 , ≤ 2.08 (custom)
    Create a notification for this product.
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-02T06:55:03.291Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_transferred"
                ],
                "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-173-03"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2023-3329",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-10-29T17:48:36.940300Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "problemTypes": [
              {
                "descriptions": [
                  {
                    "cweId": "CWE-22",
                    "description": "CWE-22 Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)",
                    "lang": "en",
                    "type": "CWE"
                  }
                ]
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-10-29T17:48:43.098Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "SCADAWebServer",
              "vendor": "iniNet",
              "versions": [
                {
                  "lessThanOrEqual": "2.08",
                  "status": "affected",
                  "version": "0",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "SpiderControl SCADA Webserver versions 2.08 and prior are vulnerable to path traversal. An attacker with administrative privileges could overwrite files on the webserver using the HMI\u0027s upload file feature. This could create size zero files anywhere on the webserver, potentially overwriting system files and creating a denial-of-service condition."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "description": "CWE-22 Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)",
                  "lang": "en"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2023-08-02T22:26:07.157Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-173-03"
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "title": "CVE-2023-3329",
          "x_generator": {
            "engine": "VINCE 2.1.3",
            "env": "prod",
            "origin": "https://cveawg.mitre.org/api/cve/CVE-2023-3329"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2023-3329",
        "datePublished": "2023-08-02T22:26:07.157Z",
        "dateReserved": "2023-06-19T17:52:02.498Z",
        "dateUpdated": "2024-10-29T17:48:43.098Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2018-18991 (GCVE-0-2018-18991)

    Vulnerability from nvd – Published: 2018-12-04 21:00 – Updated: 2024-08-05 11:23
    VLAI
    Summary
    Reflected cross-site scripting (non-persistent) in SCADA WebServer (Versions prior to 2.03.0001) could allow an attacker to send a crafted URL that contains JavaScript, which can be reflected off the web application to the victim's browser.
    Severity
    No CVSS data available.
    CWE
    • CWE-79 - IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-SITE SCRIPTING') CWE-79
    References
    Impacted products
    Vendor Product Version
    n/a SCADA WebServer Affected: Versions prior to 2.03.0001
    Date Public
    2018-12-04 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T11:23:08.950Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "name": "106105",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/106105"
              },
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-18-338-02"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "SCADA WebServer",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "Versions prior to 2.03.0001"
                }
              ]
            }
          ],
          "datePublic": "2018-12-04T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "Reflected cross-site scripting (non-persistent) in SCADA WebServer (Versions prior to 2.03.0001) could allow an attacker to send a crafted URL that contains JavaScript, which can be reflected off the web application to the victim\u0027s browser."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-79",
                  "description": "IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION (\u0027CROSS-SITE SCRIPTING\u0027) CWE-79",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2018-12-06T10:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "name": "106105",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/106105"
            },
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-18-338-02"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2018-18991",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "SCADA WebServer",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Versions prior to 2.03.0001"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "Reflected cross-site scripting (non-persistent) in SCADA WebServer (Versions prior to 2.03.0001) could allow an attacker to send a crafted URL that contains JavaScript, which can be reflected off the web application to the victim\u0027s browser."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION (\u0027CROSS-SITE SCRIPTING\u0027) CWE-79"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "106105",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/106105"
                },
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-18-338-02",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-18-338-02"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2018-18991",
        "datePublished": "2018-12-04T21:00:00.000Z",
        "dateReserved": "2018-11-06T00:00:00.000Z",
        "dateUpdated": "2024-08-05T11:23:08.950Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2017-14010 (GCVE-0-2017-14010)

    Vulnerability from nvd – Published: 2018-04-26 19:00 – Updated: 2024-09-16 21:04
    VLAI
    Summary
    In SpiderControl MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior, an uncontrolled search path element vulnerability has been identified which could be exploited by placing a specially crafted DLL file in the search path. If the malicious DLL is loaded prior to the valid DLL, an attacker could execute arbitrary code on the system.
    Severity
    No CVSS data available.
    CWE
    • CWE-427 - UNCONTROLLED SEARCH PATH ELEMENT CWE-427
    Impacted products
    Vendor Product Version
    SpiderControl MicroBrowser Affected: MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior.
    Create a notification for this product.
    Date Public
    2017-10-19 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T19:13:41.628Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-292-01"
              },
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "http://spidercontrol.net/download/downloadarea/?lang=en"
              },
              {
                "name": "101505",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/101505"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "MicroBrowser",
              "vendor": "SpiderControl",
              "versions": [
                {
                  "status": "affected",
                  "version": "MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior."
                }
              ]
            }
          ],
          "datePublic": "2017-10-19T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "In SpiderControl MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior, an uncontrolled search path element vulnerability has been identified which could be exploited by placing a specially crafted DLL file in the search path.  If the malicious DLL is loaded prior to the valid DLL, an attacker could execute arbitrary code on the system."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-427",
                  "description": "UNCONTROLLED SEARCH PATH ELEMENT CWE-427",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2018-04-27T09:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-292-01"
            },
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "http://spidercontrol.net/download/downloadarea/?lang=en"
            },
            {
              "name": "101505",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/101505"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "DATE_PUBLIC": "2017-10-19T00:00:00",
              "ID": "CVE-2017-14010",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "MicroBrowser",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior."
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "SpiderControl"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "In SpiderControl MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior, an uncontrolled search path element vulnerability has been identified which could be exploited by placing a specially crafted DLL file in the search path.  If the malicious DLL is loaded prior to the valid DLL, an attacker could execute arbitrary code on the system."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "UNCONTROLLED SEARCH PATH ELEMENT CWE-427"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-17-292-01",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-292-01"
                },
                {
                  "name": "http://spidercontrol.net/download/downloadarea/?lang=en",
                  "refsource": "MISC",
                  "url": "http://spidercontrol.net/download/downloadarea/?lang=en"
                },
                {
                  "name": "101505",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/101505"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2017-14010",
        "datePublished": "2018-04-26T19:00:00.000Z",
        "dateReserved": "2017-08-30T00:00:00.000Z",
        "dateUpdated": "2024-09-16T21:04:09.236Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2017-13995 (GCVE-0-2017-13995)

    Vulnerability from nvd – Published: 2017-10-04 07:00 – Updated: 2024-08-05 19:13
    VLAI
    Summary
    An Improper Authentication issue was discovered in iniNet Solutions iniNet Webserver, all versions prior to V2.02.0100. The webserver does not properly authenticate users, which may allow a malicious attacker to access sensitive information such as HMI pages or modify PLC variables.
    Severity
    No CVSS data available.
    CWE
    References
    Impacted products
    Vendor Product Version
    n/a iniNet Solutions GmbH SCADA Webserver Affected: iniNet Solutions GmbH SCADA Webserver
    Date Public
    2017-10-03 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T19:13:41.584Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "name": "100951",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/100951"
              },
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-264-04"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "iniNet Solutions GmbH SCADA Webserver",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "iniNet Solutions GmbH SCADA Webserver"
                }
              ]
            }
          ],
          "datePublic": "2017-10-03T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "An Improper Authentication issue was discovered in iniNet Solutions iniNet Webserver, all versions prior to V2.02.0100. The webserver does not properly authenticate users, which may allow a malicious attacker to access sensitive information such as HMI pages or modify PLC variables."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-287",
                  "description": "CWE-287",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2017-10-04T09:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "name": "100951",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/100951"
            },
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-264-04"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2017-13995",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "iniNet Solutions GmbH SCADA Webserver",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "iniNet Solutions GmbH SCADA Webserver"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "An Improper Authentication issue was discovered in iniNet Solutions iniNet Webserver, all versions prior to V2.02.0100. The webserver does not properly authenticate users, which may allow a malicious attacker to access sensitive information such as HMI pages or modify PLC variables."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-287"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "100951",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/100951"
                },
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-17-264-04",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-264-04"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2017-13995",
        "datePublished": "2017-10-04T07:00:00.000Z",
        "dateReserved": "2017-08-30T00:00:00.000Z",
        "dateUpdated": "2024-08-05T19:13:41.584Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2017-12728 (GCVE-0-2017-12728)

    Vulnerability from nvd – Published: 2017-10-04 07:00 – Updated: 2024-08-05 18:43
    VLAI
    Summary
    An Improper Privilege Management issue was discovered in SpiderControl SCADA Web Server Version 2.02.0007 and prior. Authenticated, non-administrative local users are able to alter service executables with escalated privileges, which could allow an attacker to execute arbitrary code under the context of the current system services.
    Severity
    No CVSS data available.
    CWE
    References
    Impacted products
    Vendor Product Version
    n/a SpiderControl SCADA Web Server Affected: SpiderControl SCADA Web Server
    Date Public
    2017-10-04 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T18:43:56.611Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-250-01"
              },
              {
                "name": "100668",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/100668"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "SpiderControl SCADA Web Server",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "SpiderControl SCADA Web Server"
                }
              ]
            }
          ],
          "datePublic": "2017-10-04T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "An Improper Privilege Management issue was discovered in SpiderControl SCADA Web Server Version 2.02.0007 and prior. Authenticated, non-administrative local users are able to alter service executables with escalated privileges, which could allow an attacker to execute arbitrary code under the context of the current system services."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-269",
                  "description": "CWE-269",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2017-10-04T09:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-250-01"
            },
            {
              "name": "100668",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/100668"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2017-12728",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "SpiderControl SCADA Web Server",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "SpiderControl SCADA Web Server"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "An Improper Privilege Management issue was discovered in SpiderControl SCADA Web Server Version 2.02.0007 and prior. Authenticated, non-administrative local users are able to alter service executables with escalated privileges, which could allow an attacker to execute arbitrary code under the context of the current system services."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-269"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-17-250-01",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-250-01"
                },
                {
                  "name": "100668",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/100668"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2017-12728",
        "datePublished": "2017-10-04T07:00:00.000Z",
        "dateReserved": "2017-08-09T00:00:00.000Z",
        "dateUpdated": "2024-08-05T18:43:56.611Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2017-12707 (GCVE-0-2017-12707)

    Vulnerability from nvd – Published: 2017-08-25 19:00 – Updated: 2024-08-05 18:43
    VLAI
    Summary
    A Stack-based Buffer Overflow issue was discovered in SpiderControl SCADA MicroBrowser Versions 1.6.30.144 and prior. Opening a maliciously crafted html file may cause a stack overflow.
    Severity
    No CVSS data available.
    CWE
    References
    Impacted products
    Vendor Product Version
    n/a SpiderControl SCADA MicroBrowser Affected: SpiderControl SCADA MicroBrowser
    Date Public
    2017-08-25 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T18:43:56.479Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-02"
              },
              {
                "name": "100453",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/100453"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "SpiderControl SCADA MicroBrowser",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "SpiderControl SCADA MicroBrowser"
                }
              ]
            }
          ],
          "datePublic": "2017-08-25T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "A Stack-based Buffer Overflow issue was discovered in SpiderControl SCADA MicroBrowser Versions 1.6.30.144 and prior. Opening a maliciously crafted html file may cause a stack overflow."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-121",
                  "description": "CWE-121",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2017-08-26T09:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-02"
            },
            {
              "name": "100453",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/100453"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2017-12707",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "SpiderControl SCADA MicroBrowser",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "SpiderControl SCADA MicroBrowser"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "A Stack-based Buffer Overflow issue was discovered in SpiderControl SCADA MicroBrowser Versions 1.6.30.144 and prior. Opening a maliciously crafted html file may cause a stack overflow."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-121"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-02",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-02"
                },
                {
                  "name": "100453",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/100453"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2017-12707",
        "datePublished": "2017-08-25T19:00:00.000Z",
        "dateReserved": "2017-08-09T00:00:00.000Z",
        "dateUpdated": "2024-08-05T18:43:56.479Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2017-12694 (GCVE-0-2017-12694)

    Vulnerability from nvd – Published: 2017-08-25 19:00 – Updated: 2024-08-05 18:43
    VLAI
    Summary
    A Directory Traversal issue was discovered in SpiderControl SCADA Web Server. An attacker may be able to use a simple GET request to perform a directory traversal into system files.
    Severity
    No CVSS data available.
    CWE
    References
    Impacted products
    Vendor Product Version
    n/a SpiderControl SCADA Web Server Affected: SpiderControl SCADA Web Server
    Date Public
    2017-08-25 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T18:43:56.452Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-03"
              },
              {
                "name": "100456",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/100456"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "SpiderControl SCADA Web Server",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "SpiderControl SCADA Web Server"
                }
              ]
            }
          ],
          "datePublic": "2017-08-25T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "A Directory Traversal issue was discovered in SpiderControl SCADA Web Server. An attacker may be able to use a simple GET request to perform a directory traversal into system files."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-22",
                  "description": "CWE-22",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2017-08-26T09:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-03"
            },
            {
              "name": "100456",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/100456"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2017-12694",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "SpiderControl SCADA Web Server",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "SpiderControl SCADA Web Server"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "A Directory Traversal issue was discovered in SpiderControl SCADA Web Server. An attacker may be able to use a simple GET request to perform a directory traversal into system files."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-22"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-03",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-03"
                },
                {
                  "name": "100456",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/100456"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2017-12694",
        "datePublished": "2017-08-25T19:00:00.000Z",
        "dateReserved": "2017-08-09T00:00:00.000Z",
        "dateUpdated": "2024-08-05T18:43:56.452Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2024-10313 (GCVE-0-2024-10313)

    Vulnerability from cvelistv5 – Published: 2024-10-24 17:41 – Updated: 2024-10-24 18:29
    VLAI
    Title
    iniNet Solutions SpiderControl SCADA PC HMI Editor Path Traversal
    Summary
    iniNet Solutions SpiderControl SCADA PC HMI Editor has a path traversal vulnerability. When the software loads a malicious ‘ems' project template file constructed by an attacker, it can write files to arbitrary directories. This can lead to overwriting system files, causing system paralysis, or writing to startup items, resulting in remote control.
    SSVC
    Exploitation: none Automatable: no Technical Impact: total
    CISA Coordinator · CISA-ADP (v2.0.3)
    Decision recorded 2024-10-24 18:23 UTC
    CWE
    Impacted products
    Vendor Product Version
    iniNet Solutions SpiderControl SCADA PC HMI Editor Affected: 8.10.00.00
    Create a notification for this product.
    spidercontrol scada_pc_hmi_editor Affected: 8.10.00.00
        cpe:2.3:a:spidercontrol:scada_pc_hmi_editor:*:*:*:*:*:*:*:*
    Create a notification for this product.
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "affected": [
              {
                "cpes": [
                  "cpe:2.3:a:spidercontrol:scada_pc_hmi_editor:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unaffected",
                "product": "scada_pc_hmi_editor",
                "vendor": "spidercontrol",
                "versions": [
                  {
                    "status": "affected",
                    "version": "8.10.00.00"
                  }
                ]
              }
            ],
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2024-10313",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-10-24T18:23:13.626806Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-10-24T18:29:45.979Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "SpiderControl SCADA PC HMI Editor",
              "vendor": "iniNet Solutions",
              "versions": [
                {
                  "status": "affected",
                  "version": "8.10.00.00"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "finder",
              "value": "elcazator from ELEX FEIGONG RESEARCH INSTITUTE of Elex CyberSecurity, Inc. reported this vulnerability to CISA."
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "iniNet Solutions SpiderControl SCADA PC HMI Editor has a path traversal \nvulnerability. When the software loads a malicious \u2018ems\u0027 project \ntemplate file constructed by an attacker, it can write files to \narbitrary directories. This can lead to overwriting system files, \ncausing system paralysis, or writing to startup items, resulting in \nremote control."
                }
              ],
              "value": "iniNet Solutions SpiderControl SCADA PC HMI Editor has a path traversal \nvulnerability. When the software loads a malicious \u2018ems\u0027 project \ntemplate file constructed by an attacker, it can write files to \narbitrary directories. This can lead to overwriting system files, \ncausing system paralysis, or writing to startup items, resulting in \nremote control."
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 8,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "HIGH",
                "integrityImpact": "HIGH",
                "privilegesRequired": "LOW",
                "scope": "UNCHANGED",
                "userInteraction": "REQUIRED",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H",
                "version": "3.1"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            },
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 8.6,
                "baseSeverity": "HIGH",
                "privilegesRequired": "LOW",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "PASSIVE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "HIGH",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-22",
                  "description": "CWE-22 Path Traversal",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2024-10-24T17:41:56.069Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-298-02"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "iniNet Solutions recommends that users update SpiderControl SCADA PC HMI Editor to version \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://spidercontrol.net/download/download-area-2/?lang=en#editor\"\u003e8.24.00.00\u003c/a\u003e to mitigate this vulnerability.\n\n\u003cbr\u003e"
                }
              ],
              "value": "iniNet Solutions recommends that users update SpiderControl SCADA PC HMI Editor to version  8.24.00.00 https://spidercontrol.net/download/download-area-2/  to mitigate this vulnerability."
            }
          ],
          "source": {
            "advisory": "ICSA-24-298-02",
            "discovery": "EXTERNAL"
          },
          "title": "iniNet Solutions SpiderControl SCADA PC HMI Editor Path Traversal",
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2024-10313",
        "datePublished": "2024-10-24T17:41:56.069Z",
        "dateReserved": "2024-10-23T18:25:15.297Z",
        "dateUpdated": "2024-10-24T18:29:45.979Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2024-8232 (GCVE-0-2024-8232)

    Vulnerability from cvelistv5 – Published: 2024-09-10 19:44 – Updated: 2024-09-12 13:36
    VLAI
    Title
    iniNet Solutions SpiderControl SCADA Web Server Unrestricted Upload of File with Dangerous Type
    Summary
    SpiderControl SCADA Web Server has a vulnerability that could allow an attacker to upload specially crafted malicious files without authentication.
    SSVC
    Exploitation: none Automatable: yes Technical Impact: partial
    CISA Coordinator · CISA-ADP (v2.0.3)
    Decision recorded 2024-09-12 13:34 UTC
    CWE
    • CWE-434 - Unrestricted Upload of File with Dangerous Type
    Impacted products
    Vendor Product Version
    iniNet Solutions GmbH SpiderControl SCADA Web Server Affected: 0 , ≤ v2.09 (custom)
    Create a notification for this product.
    spidercontrol scada_webserver Affected: 0 , ≤ 2.09 (custom)
        cpe:2.3:a:spidercontrol:scada_webserver:*:*:*:*:*:*:*:*
    Create a notification for this product.
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "affected": [
              {
                "cpes": [
                  "cpe:2.3:a:spidercontrol:scada_webserver:*:*:*:*:*:*:*:*"
                ],
                "defaultStatus": "unaffected",
                "product": "scada_webserver",
                "vendor": "spidercontrol",
                "versions": [
                  {
                    "lessThanOrEqual": "2.09",
                    "status": "affected",
                    "version": "0",
                    "versionType": "custom"
                  }
                ]
              }
            ],
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2024-8232",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-09-12T13:34:02.939872Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-09-12T13:36:10.295Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "SpiderControl SCADA Web Server",
              "vendor": "iniNet Solutions GmbH",
              "versions": [
                {
                  "lessThanOrEqual": "v2.09",
                  "status": "affected",
                  "version": "0",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "type": "finder",
              "value": "elcazators ELEX FEIGONG RESEARCH INSTITUTE of Elex CyberSecurity, Inc reported this vulnerability to CERT/CC."
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "SpiderControl SCADA Web Server has a vulnerability that could allow an \nattacker to upload specially crafted malicious files without \nauthentication."
                }
              ],
              "value": "SpiderControl SCADA Web Server has a vulnerability that could allow an \nattacker to upload specially crafted malicious files without \nauthentication."
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "NONE",
                "baseScore": 7.5,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "HIGH",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
                "version": "3.1"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            },
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 8.7,
                "baseSeverity": "HIGH",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "NONE",
                "vulnConfidentialityImpact": "NONE",
                "vulnIntegrityImpact": "HIGH",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-434",
                  "description": "CWE-434 Unrestricted Upload of File with Dangerous Type",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2024-09-10T19:44:18.096Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-254-02"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "IniNet Solutions has released a new version of SpiderControl SCADA \nServer, (3.2.2), to address this issue. It can be found at the following\n location: \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://spidercontrol.net/download/download-area-2/?lang=en\"\u003ehttps://spidercontrol.net/download/download-area-2/?lang=en\u003c/a\u003e\n\n\u003cbr\u003e"
                }
              ],
              "value": "IniNet Solutions has released a new version of SpiderControl SCADA \nServer, (3.2.2), to address this issue. It can be found at the following\n location:  https://spidercontrol.net/download/download-area-2/?lang=en"
            }
          ],
          "source": {
            "advisory": "ICSA-24-254-02",
            "discovery": "EXTERNAL"
          },
          "title": "iniNet Solutions SpiderControl SCADA Web Server Unrestricted Upload of File with Dangerous Type",
          "workarounds": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "IniNet Solutions reminds users that the webserver is designed to be used\n in a protected environment. IniNet Solutions GmbH recommends that users\n never connect control system software directly to the Internet. If a \nuser must connect to the Internet, IniNet Solutions GmbH recommends \nusing a managed infrastructure to do so.\n\n\u003cbr\u003e"
                }
              ],
              "value": "IniNet Solutions reminds users that the webserver is designed to be used\n in a protected environment. IniNet Solutions GmbH recommends that users\n never connect control system software directly to the Internet. If a \nuser must connect to the Internet, IniNet Solutions GmbH recommends \nusing a managed infrastructure to do so."
            }
          ],
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2024-8232",
        "datePublished": "2024-09-10T19:44:18.096Z",
        "dateReserved": "2024-08-27T13:40:41.730Z",
        "dateUpdated": "2024-09-12T13:36:10.295Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2023-3329 (GCVE-0-2023-3329)

    Vulnerability from cvelistv5 – Published: 2023-08-02 22:26 – Updated: 2024-10-29 17:48
    VLAI
    Title
    CVE-2023-3329
    Summary
    SpiderControl SCADA Webserver versions 2.08 and prior are vulnerable to path traversal. An attacker with administrative privileges could overwrite files on the webserver using the HMI's upload file feature. This could create size zero files anywhere on the webserver, potentially overwriting system files and creating a denial-of-service condition.
    Severity
    No CVSS data available.
    SSVC
    Exploitation: none Automatable: no Technical Impact: total
    CISA Coordinator · CISA-ADP (v2.0.3)
    Decision recorded 2024-10-29 17:48 UTC
    CWE
    Impacted products
    Vendor Product Version
    iniNet SCADAWebServer Affected: 0 , ≤ 2.08 (custom)
    Create a notification for this product.
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-02T06:55:03.291Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_transferred"
                ],
                "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-173-03"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2023-3329",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2024-10-29T17:48:36.940300Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "problemTypes": [
              {
                "descriptions": [
                  {
                    "cweId": "CWE-22",
                    "description": "CWE-22 Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)",
                    "lang": "en",
                    "type": "CWE"
                  }
                ]
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2024-10-29T17:48:43.098Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "SCADAWebServer",
              "vendor": "iniNet",
              "versions": [
                {
                  "lessThanOrEqual": "2.08",
                  "status": "affected",
                  "version": "0",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "SpiderControl SCADA Webserver versions 2.08 and prior are vulnerable to path traversal. An attacker with administrative privileges could overwrite files on the webserver using the HMI\u0027s upload file feature. This could create size zero files anywhere on the webserver, potentially overwriting system files and creating a denial-of-service condition."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "description": "CWE-22 Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)",
                  "lang": "en"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2023-08-02T22:26:07.157Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-173-03"
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "title": "CVE-2023-3329",
          "x_generator": {
            "engine": "VINCE 2.1.3",
            "env": "prod",
            "origin": "https://cveawg.mitre.org/api/cve/CVE-2023-3329"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2023-3329",
        "datePublished": "2023-08-02T22:26:07.157Z",
        "dateReserved": "2023-06-19T17:52:02.498Z",
        "dateUpdated": "2024-10-29T17:48:43.098Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2018-18991 (GCVE-0-2018-18991)

    Vulnerability from cvelistv5 – Published: 2018-12-04 21:00 – Updated: 2024-08-05 11:23
    VLAI
    Summary
    Reflected cross-site scripting (non-persistent) in SCADA WebServer (Versions prior to 2.03.0001) could allow an attacker to send a crafted URL that contains JavaScript, which can be reflected off the web application to the victim's browser.
    Severity
    No CVSS data available.
    CWE
    • CWE-79 - IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-SITE SCRIPTING') CWE-79
    References
    Impacted products
    Vendor Product Version
    n/a SCADA WebServer Affected: Versions prior to 2.03.0001
    Date Public
    2018-12-04 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T11:23:08.950Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "name": "106105",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/106105"
              },
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-18-338-02"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "SCADA WebServer",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "Versions prior to 2.03.0001"
                }
              ]
            }
          ],
          "datePublic": "2018-12-04T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "Reflected cross-site scripting (non-persistent) in SCADA WebServer (Versions prior to 2.03.0001) could allow an attacker to send a crafted URL that contains JavaScript, which can be reflected off the web application to the victim\u0027s browser."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-79",
                  "description": "IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION (\u0027CROSS-SITE SCRIPTING\u0027) CWE-79",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2018-12-06T10:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "name": "106105",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/106105"
            },
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-18-338-02"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2018-18991",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "SCADA WebServer",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Versions prior to 2.03.0001"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "Reflected cross-site scripting (non-persistent) in SCADA WebServer (Versions prior to 2.03.0001) could allow an attacker to send a crafted URL that contains JavaScript, which can be reflected off the web application to the victim\u0027s browser."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION (\u0027CROSS-SITE SCRIPTING\u0027) CWE-79"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "106105",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/106105"
                },
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-18-338-02",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-18-338-02"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2018-18991",
        "datePublished": "2018-12-04T21:00:00.000Z",
        "dateReserved": "2018-11-06T00:00:00.000Z",
        "dateUpdated": "2024-08-05T11:23:08.950Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2017-14010 (GCVE-0-2017-14010)

    Vulnerability from cvelistv5 – Published: 2018-04-26 19:00 – Updated: 2024-09-16 21:04
    VLAI
    Summary
    In SpiderControl MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior, an uncontrolled search path element vulnerability has been identified which could be exploited by placing a specially crafted DLL file in the search path. If the malicious DLL is loaded prior to the valid DLL, an attacker could execute arbitrary code on the system.
    Severity
    No CVSS data available.
    CWE
    • CWE-427 - UNCONTROLLED SEARCH PATH ELEMENT CWE-427
    Impacted products
    Vendor Product Version
    SpiderControl MicroBrowser Affected: MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior.
    Create a notification for this product.
    Date Public
    2017-10-19 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T19:13:41.628Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-292-01"
              },
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "http://spidercontrol.net/download/downloadarea/?lang=en"
              },
              {
                "name": "101505",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/101505"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "MicroBrowser",
              "vendor": "SpiderControl",
              "versions": [
                {
                  "status": "affected",
                  "version": "MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior."
                }
              ]
            }
          ],
          "datePublic": "2017-10-19T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "In SpiderControl MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior, an uncontrolled search path element vulnerability has been identified which could be exploited by placing a specially crafted DLL file in the search path.  If the malicious DLL is loaded prior to the valid DLL, an attacker could execute arbitrary code on the system."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-427",
                  "description": "UNCONTROLLED SEARCH PATH ELEMENT CWE-427",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2018-04-27T09:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-292-01"
            },
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "http://spidercontrol.net/download/downloadarea/?lang=en"
            },
            {
              "name": "101505",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/101505"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "DATE_PUBLIC": "2017-10-19T00:00:00",
              "ID": "CVE-2017-14010",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "MicroBrowser",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior."
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "SpiderControl"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "In SpiderControl MicroBrowser Windows XP, Vista 7, 8 and 10, Versions 1.6.30.144 and prior, an uncontrolled search path element vulnerability has been identified which could be exploited by placing a specially crafted DLL file in the search path.  If the malicious DLL is loaded prior to the valid DLL, an attacker could execute arbitrary code on the system."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "UNCONTROLLED SEARCH PATH ELEMENT CWE-427"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-17-292-01",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-292-01"
                },
                {
                  "name": "http://spidercontrol.net/download/downloadarea/?lang=en",
                  "refsource": "MISC",
                  "url": "http://spidercontrol.net/download/downloadarea/?lang=en"
                },
                {
                  "name": "101505",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/101505"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2017-14010",
        "datePublished": "2018-04-26T19:00:00.000Z",
        "dateReserved": "2017-08-30T00:00:00.000Z",
        "dateUpdated": "2024-09-16T21:04:09.236Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2017-13995 (GCVE-0-2017-13995)

    Vulnerability from cvelistv5 – Published: 2017-10-04 07:00 – Updated: 2024-08-05 19:13
    VLAI
    Summary
    An Improper Authentication issue was discovered in iniNet Solutions iniNet Webserver, all versions prior to V2.02.0100. The webserver does not properly authenticate users, which may allow a malicious attacker to access sensitive information such as HMI pages or modify PLC variables.
    Severity
    No CVSS data available.
    CWE
    References
    Impacted products
    Vendor Product Version
    n/a iniNet Solutions GmbH SCADA Webserver Affected: iniNet Solutions GmbH SCADA Webserver
    Date Public
    2017-10-03 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T19:13:41.584Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "name": "100951",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/100951"
              },
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-264-04"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "iniNet Solutions GmbH SCADA Webserver",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "iniNet Solutions GmbH SCADA Webserver"
                }
              ]
            }
          ],
          "datePublic": "2017-10-03T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "An Improper Authentication issue was discovered in iniNet Solutions iniNet Webserver, all versions prior to V2.02.0100. The webserver does not properly authenticate users, which may allow a malicious attacker to access sensitive information such as HMI pages or modify PLC variables."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-287",
                  "description": "CWE-287",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2017-10-04T09:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "name": "100951",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/100951"
            },
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-264-04"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2017-13995",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "iniNet Solutions GmbH SCADA Webserver",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "iniNet Solutions GmbH SCADA Webserver"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "An Improper Authentication issue was discovered in iniNet Solutions iniNet Webserver, all versions prior to V2.02.0100. The webserver does not properly authenticate users, which may allow a malicious attacker to access sensitive information such as HMI pages or modify PLC variables."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-287"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "100951",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/100951"
                },
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-17-264-04",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-264-04"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2017-13995",
        "datePublished": "2017-10-04T07:00:00.000Z",
        "dateReserved": "2017-08-30T00:00:00.000Z",
        "dateUpdated": "2024-08-05T19:13:41.584Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2017-12728 (GCVE-0-2017-12728)

    Vulnerability from cvelistv5 – Published: 2017-10-04 07:00 – Updated: 2024-08-05 18:43
    VLAI
    Summary
    An Improper Privilege Management issue was discovered in SpiderControl SCADA Web Server Version 2.02.0007 and prior. Authenticated, non-administrative local users are able to alter service executables with escalated privileges, which could allow an attacker to execute arbitrary code under the context of the current system services.
    Severity
    No CVSS data available.
    CWE
    References
    Impacted products
    Vendor Product Version
    n/a SpiderControl SCADA Web Server Affected: SpiderControl SCADA Web Server
    Date Public
    2017-10-04 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T18:43:56.611Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-250-01"
              },
              {
                "name": "100668",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/100668"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "SpiderControl SCADA Web Server",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "SpiderControl SCADA Web Server"
                }
              ]
            }
          ],
          "datePublic": "2017-10-04T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "An Improper Privilege Management issue was discovered in SpiderControl SCADA Web Server Version 2.02.0007 and prior. Authenticated, non-administrative local users are able to alter service executables with escalated privileges, which could allow an attacker to execute arbitrary code under the context of the current system services."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-269",
                  "description": "CWE-269",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2017-10-04T09:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-250-01"
            },
            {
              "name": "100668",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/100668"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2017-12728",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "SpiderControl SCADA Web Server",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "SpiderControl SCADA Web Server"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "An Improper Privilege Management issue was discovered in SpiderControl SCADA Web Server Version 2.02.0007 and prior. Authenticated, non-administrative local users are able to alter service executables with escalated privileges, which could allow an attacker to execute arbitrary code under the context of the current system services."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-269"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-17-250-01",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-250-01"
                },
                {
                  "name": "100668",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/100668"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2017-12728",
        "datePublished": "2017-10-04T07:00:00.000Z",
        "dateReserved": "2017-08-09T00:00:00.000Z",
        "dateUpdated": "2024-08-05T18:43:56.611Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2017-12694 (GCVE-0-2017-12694)

    Vulnerability from cvelistv5 – Published: 2017-08-25 19:00 – Updated: 2024-08-05 18:43
    VLAI
    Summary
    A Directory Traversal issue was discovered in SpiderControl SCADA Web Server. An attacker may be able to use a simple GET request to perform a directory traversal into system files.
    Severity
    No CVSS data available.
    CWE
    References
    Impacted products
    Vendor Product Version
    n/a SpiderControl SCADA Web Server Affected: SpiderControl SCADA Web Server
    Date Public
    2017-08-25 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T18:43:56.452Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-03"
              },
              {
                "name": "100456",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/100456"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "SpiderControl SCADA Web Server",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "SpiderControl SCADA Web Server"
                }
              ]
            }
          ],
          "datePublic": "2017-08-25T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "A Directory Traversal issue was discovered in SpiderControl SCADA Web Server. An attacker may be able to use a simple GET request to perform a directory traversal into system files."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-22",
                  "description": "CWE-22",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2017-08-26T09:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-03"
            },
            {
              "name": "100456",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/100456"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2017-12694",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "SpiderControl SCADA Web Server",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "SpiderControl SCADA Web Server"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "A Directory Traversal issue was discovered in SpiderControl SCADA Web Server. An attacker may be able to use a simple GET request to perform a directory traversal into system files."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-22"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-03",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-03"
                },
                {
                  "name": "100456",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/100456"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2017-12694",
        "datePublished": "2017-08-25T19:00:00.000Z",
        "dateReserved": "2017-08-09T00:00:00.000Z",
        "dateUpdated": "2024-08-05T18:43:56.452Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2017-12707 (GCVE-0-2017-12707)

    Vulnerability from cvelistv5 – Published: 2017-08-25 19:00 – Updated: 2024-08-05 18:43
    VLAI
    Summary
    A Stack-based Buffer Overflow issue was discovered in SpiderControl SCADA MicroBrowser Versions 1.6.30.144 and prior. Opening a maliciously crafted html file may cause a stack overflow.
    Severity
    No CVSS data available.
    CWE
    References
    Impacted products
    Vendor Product Version
    n/a SpiderControl SCADA MicroBrowser Affected: SpiderControl SCADA MicroBrowser
    Date Public
    2017-08-25 00:00
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T18:43:56.479Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_MISC",
                  "x_transferred"
                ],
                "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-02"
              },
              {
                "name": "100453",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/100453"
              }
            ],
            "title": "CVE Program Container"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "SpiderControl SCADA MicroBrowser",
              "vendor": "n/a",
              "versions": [
                {
                  "status": "affected",
                  "version": "SpiderControl SCADA MicroBrowser"
                }
              ]
            }
          ],
          "datePublic": "2017-08-25T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "A Stack-based Buffer Overflow issue was discovered in SpiderControl SCADA MicroBrowser Versions 1.6.30.144 and prior. Opening a maliciously crafted html file may cause a stack overflow."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-121",
                  "description": "CWE-121",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2017-08-26T09:57:01.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_MISC"
              ],
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-02"
            },
            {
              "name": "100453",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/100453"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "ID": "CVE-2017-12707",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "SpiderControl SCADA MicroBrowser",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "SpiderControl SCADA MicroBrowser"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "n/a"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "A Stack-based Buffer Overflow issue was discovered in SpiderControl SCADA MicroBrowser Versions 1.6.30.144 and prior. Opening a maliciously crafted html file may cause a stack overflow."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-121"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-02",
                  "refsource": "MISC",
                  "url": "https://ics-cert.us-cert.gov/advisories/ICSA-17-234-02"
                },
                {
                  "name": "100453",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/100453"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2017-12707",
        "datePublished": "2017-08-25T19:00:00.000Z",
        "dateReserved": "2017-08-09T00:00:00.000Z",
        "dateUpdated": "2024-08-05T18:43:56.479Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }