ICSA-26-321-01

Vulnerability from csaf_cisa - Published: 2026-11-17 06:00 - Updated: 2026-11-17 06:00
Summary
Dorsett Controls InfoScan
Notes
Countries/areas deployed: Worldwide
Company headquarters location: United States
Critical infrastructure sectors: Water and Wastewater Systems
Advisory Summary: Successful exploitation of these vulnerabilities could allow an attacker to retrieve sensitive system information, access application data without authorization, recover stored credentials, or intercept and manipulate network communications.
Legal Notice and Terms of Use: This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).
Recommended Practices: CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.
Recommended Practices: Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Recommended Practices: Locate control system networks and remote devices behind firewalls and isolating them from business networks.
Recommended Practices: When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
Recommended Practices: CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices: CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices: CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Recommended Practices: Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices: Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices: CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
Recommended Practices: No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
CWE-295 - Improper Certificate Validation
Affected products
Product Identifier Version Remediation
Dorsett Controls InfoScan <=1.45.0
Dorsett Controls / InfoScan
<=1.45.0
Vendor Fix fix
CWE-497 - Exposure of Sensitive System Information to an Unauthorized Control Sphere
Affected products
Known affected 1 product, the same list as for CVE-2026-117659
CWE-321 - Use of Hard-coded Cryptographic Key
Affected products
Known affected 1 product, the same list as for CVE-2026-117659
CWE-306 - Missing Authentication for Critical Function
Affected products
Known affected 1 product, the same list as for CVE-2026-117659
CWE-497 - Exposure of Sensitive System Information to an Unauthorized Control Sphere
Affected products
Known affected 1 product, the same list as for CVE-2026-117659
CWE-209 - Generation of Error Message Containing Sensitive Information
Affected products
Known affected 1 product, the same list as for CVE-2026-117659
Acknowledgments

{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "Cyber-Tim"
        ],
        "summary": "reported these vulnerabilities to CISA"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage"
      }
    },
    "lang": "en-us",
    "notes": [
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "United States",
        "title": "Company headquarters location"
      },
      {
        "category": "other",
        "text": "Water and Wastewater Systems",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could allow an attacker to retrieve sensitive system information, access application data without authorization, recover stored credentials, or intercept and manipulate network communications.",
        "title": "Advisory Summary"
      },
      {
        "category": "legal_disclaimer",
        "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy \u0026 Use policy (https://www.cisa.gov/privacy-policy).",
        "title": "Legal Notice and Terms of Use"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Locate control system networks and remote devices behind firewalls and isolating them from business networks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "central@cisa.dhs.gov",
      "issuing_authority": "CISA",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-26-321-01 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2026/icsa-26-321-01.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-26-321-01 - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-321-01"
      }
    ],
    "title": "Dorsett Controls InfoScan",
    "tracking": {
      "current_release_date": "2026-11-17T06:00:00.000000Z",
      "generator": {
        "date": "2026-11-17T06:00:00.000000Z",
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "2.0.0"
        }
      },
      "id": "ICSA-26-321-01",
      "initial_release_date": "2026-11-17T06:00:00.000000Z",
      "revision_history": [
        {
          "date": "2026-11-17T06:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Initial Publication"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=1.45.0",
                "product": {
                  "name": "Dorsett Controls InfoScan \u003c=1.45.0",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "InfoScan"
          }
        ],
        "category": "vendor",
        "name": "Dorsett Controls"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2026-117659",
      "cwe": {
        "id": "CWE-295",
        "name": "Improper Certificate Validation"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The InfoScan Electron desktop client improperly handles TLS certificate errors by accepting certificates without validating their trustworthiness. The client also configures Electron with nodeIntegration enabled, contextIsolation disabled, and webSecurity disabled. These settings weaken the client\u2019s security boundaries. An attacker who is able to intercept or manipulate network communications may be able to present an untrusted certificate without the application rejecting the connection.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:N/A:N/T:T/2026-11-12T18:15:18Z/",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "date": "2026-10-22T00:00:00Z",
          "details": "Dorsett Controls recommends updating affected versions of InfoScan to v1.46 or higher.\n\nTo install the security patch, user administrators will need to log in to InfoScan and select System Maintenance from the menu. Once the System Maintenance application is open, select Check for Updates, and click the Install Now button in the Ready To Install section. If you are an offline customer (InfoScan has no internet access), you will need to download the update from the Dorsett Controls Customer Portal by selecting the InfoScan Update tile, downloading the update, and following the instructions listed on the portal.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://portal.dtscada.com/#/security-bulletins"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.1,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ],
      "title": "The InfoScan Electron desktop client improperly handles TLS certificate errors by accepting certificates without validating their trustworthiness. The client also configures Electron with nodeIntegration enabled, contextIsolation disabled, and webSecurity disabled. These settings weaken the client\u2019s security boundaries. An attacker who is able to intercept or manipulate network communications may be able to present an untrusted certificate without the application rejecting the connection."
    },
    {
      "cve": "CVE-2026-120157",
      "cwe": {
        "id": "CWE-497",
        "name": "Exposure of Sensitive System Information to an Unauthorized Control Sphere"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The publicly distributed InfoScan Electron installer contains configuration files identifying hostnames associated with customer installations and internal development, testing, and database infrastructure. An individual who obtains and inspects the installer can extract these hostnames without authenticating to the affected systems.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:N/A:Y/T:P/2026-11-09T14:49:52Z/",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "date": "2026-10-22T00:00:00Z",
          "details": "Dorsett Controls recommends updating affected versions of InfoScan to v1.46 or higher.\n\nTo install the security patch, user administrators will need to log in to InfoScan and select System Maintenance from the menu. Once the System Maintenance application is open, select Check for Updates, and click the Install Now button in the Ready To Install section. If you are an offline customer (InfoScan has no internet access), you will need to download the update from the Dorsett Controls Customer Portal by selecting the InfoScan Update tile, downloading the update, and following the instructions listed on the portal.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://portal.dtscada.com/#/security-bulletins"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 5.3,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ],
      "title": "The publicly distributed InfoScan Electron installer contains configuration files identifying hostnames associated with customer installations and internal development, testing, and database infrastructure. An individual who obtains and inspects the installer can extract these hostnames without authenticating to the affected systems."
    },
    {
      "cve": "CVE-2026-120255",
      "cwe": {
        "id": "CWE-321",
        "name": "Use of Hard-coded Cryptographic Key"
      },
      "notes": [
        {
          "category": "summary",
          "text": "InfoScan uses hard-coded cryptographic keys and initialization-vector values in its database-encryption implementation. The application uses these values to encrypt the MongoDB password before storing it in the Windows registry. Because the cryptographic material is embedded in the distributed application, an individual with access to the encrypted registry value and the application code may be able to recover the database password.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:N/A:N/T:P/2026-11-12T18:15:39Z/",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:A/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "date": "2026-10-22T00:00:00Z",
          "details": "Dorsett Controls recommends updating affected versions of InfoScan to v1.46 or higher.\n\nTo install the security patch, user administrators will need to log in to InfoScan and select System Maintenance from the menu. Once the System Maintenance application is open, select Check for Updates, and click the Install Now button in the Ready To Install section. If you are an offline customer (InfoScan has no internet access), you will need to download the update from the Dorsett Controls Customer Portal by selecting the InfoScan Update tile, downloading the update, and following the instructions listed on the portal.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://portal.dtscada.com/#/security-bulletins"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 4.3,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ],
      "title": "InfoScan uses hard-coded cryptographic keys and initialization-vector values in its database-encryption implementation. The application uses these values to encrypt the MongoDB password before storing it in the Windows registry. Because the cryptographic material is embedded in the distributed application, an individual with access to the encrypted registry value and the application code may be able to recover the database password."
    },
    {
      "cve": "CVE-2026-120260",
      "cwe": {
        "id": "CWE-306",
        "name": "Missing Authentication for Critical Function"
      },
      "notes": [
        {
          "category": "summary",
          "text": "InfoScan does not enforce authentication on an endpoint used to retrieve sales-automation templates. A local attacker can submit an HTTP request to the affected endpoint without a valid session and retrieve the returned template data.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:N/A:N/T:P/2026-11-12T18:15:59Z/",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "date": "2026-10-22T00:00:00Z",
          "details": "Dorsett Controls recommends updating affected versions of InfoScan to v1.46 or higher.\n\nTo install the security patch, user administrators will need to log in to InfoScan and select System Maintenance from the menu. Once the System Maintenance application is open, select Check for Updates, and click the Install Now button in the Ready To Install section. If you are an offline customer (InfoScan has no internet access), you will need to download the update from the Dorsett Controls Customer Portal by selecting the InfoScan Update tile, downloading the update, and following the instructions listed on the portal.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://portal.dtscada.com/#/security-bulletins"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 5.5,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ],
      "title": "InfoScan does not enforce authentication on an endpoint used to retrieve sales-automation templates. A local attacker can submit an HTTP request to the affected endpoint without a valid session and retrieve the returned template data."
    },
    {
      "cve": "CVE-2026-120271",
      "cwe": {
        "id": "CWE-497",
        "name": "Exposure of Sensitive System Information to an Unauthorized Control Sphere"
      },
      "notes": [
        {
          "category": "summary",
          "text": "InfoScan contains an unauthenticated information disclosure vulnerability in its mobile-enumeration and version-reporting endpoints. A remote attacker can send HTTP requests without authentication to retrieve system configuration information, including usernames and display names, multifactor authentication configuration status, session settings, application version information, server details, hardware module firmware versions, and the BACnet/IP port used by the installation.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:N/A:N/T:P/2026-11-12T18:16:13Z/",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "date": "2026-10-22T00:00:00Z",
          "details": "Dorsett Controls recommends updating affected versions of InfoScan to v1.46 or higher.\n\nTo install the security patch, user administrators will need to log in to InfoScan and select System Maintenance from the menu. Once the System Maintenance application is open, select Check for Updates, and click the Install Now button in the Ready To Install section. If you are an offline customer (InfoScan has no internet access), you will need to download the update from the Dorsett Controls Customer Portal by selecting the InfoScan Update tile, downloading the update, and following the instructions listed on the portal.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://portal.dtscada.com/#/security-bulletins"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 5.3,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ],
      "title": "InfoScan contains an unauthenticated information disclosure vulnerability in its mobile-enumeration and version-reporting endpoints. A remote attacker can send HTTP requests without authentication to retrieve system configuration information, including usernames and display names, multifactor authentication configuration status, session settings, application version information, server details, hardware module firmware versions, and the BACnet/IP port used by the installation."
    },
    {
      "cve": "CVE-2026-120298",
      "cwe": {
        "id": "CWE-209",
        "name": "Generation of Error Message Containing Sensitive Information"
      },
      "notes": [
        {
          "category": "summary",
          "text": "InfoScan fails to properly handle certain malformed or incomplete requests to its login and password-reset endpoints. These requests can trigger unhandled server exceptions that return detailed Node.js stack traces to the requester. The responses disclose internal filesystem paths, application directory names, source file locations, and line numbers.",
          "title": "Vulnerability Summary"
        },
        {
          "category": "details",
          "text": "SSVCv2/E:N/A:N/T:P/2026-11-12T18:16:36Z/",
          "title": "SSVC"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "date": "2026-10-22T00:00:00Z",
          "details": "Dorsett Controls recommends updating affected versions of InfoScan to v1.46 or higher.\n\nTo install the security patch, user administrators will need to log in to InfoScan and select System Maintenance from the menu. Once the System Maintenance application is open, select Check for Updates, and click the Install Now button in the Ready To Install section. If you are an offline customer (InfoScan has no internet access), you will need to download the update from the Dorsett Controls Customer Portal by selecting the InfoScan Update tile, downloading the update, and following the instructions listed on the portal.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://portal.dtscada.com/#/security-bulletins"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 5.3,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ],
      "title": "InfoScan fails to properly handle certain malformed or incomplete requests to its login and password-reset endpoints. These requests can trigger unhandled server exceptions that return detailed Node.js stack traces to the requester. The responses disclose internal filesystem paths, application directory names, source file locations, and line numbers."
    }
  ]
}



Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.