  <entry>
    <id>https://cve.radiocsirt.org/vuln/cve-2021-35533</id>
    <title>CVE-2021-35533 — Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series</title>
    <updated>2026-10-17T17:36:10.072940+00:00</updated>
    <content type="xhtml">
      <div xmlns="http://www.w3.org/1999/xhtml"><p><strong>Affected:</strong> Hitachi Energy RTU500 series</p>
<p>Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).</p></div>
    </content>
    <link href="https://cve.radiocsirt.org/vuln/cve-2021-35533"/>
  </entry>