  <entry>
    <id>https://cve.radiocsirt.org/vuln/cve-2022-1669</id>
    <title>CVE-2022-1669 — Circutor COMPACT DC-S BASIC</title>
    <updated>2026-10-16T19:38:52.494101+00:00</updated>
    <content type="xhtml">
      <div xmlns="http://www.w3.org/1999/xhtml"><p><strong>Affected:</strong> CIRCUTOR COMPACT DC-S BASIC</p>
<p>A buffer overflow vulnerability has been detected in the firewall function of the device management web portal. The device runs a CGI binary (index.cgi) to offer a management web application. Once authenticated with valid credentials in this web portal, a potential attacker could submit any "Address" value and it would be copied to a second variable with a "strcpy" vulnerable function without checking its length. Because of this, it is possible to send a long address value to overflow the process stack, controlling the function return address.</p></div>