<?xml version='1.0' encoding='UTF-8'?>
<?xml-stylesheet href="/static/style.xsl" type="text/xsl"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
  <id>https://cve.radiocsirt.org/rss/recent/all/10</id>
  <title>Most recent entries from all</title>
  <updated>2026-10-07T21:02:11.186967+00:00</updated>
  <author>
    <name>Vulnerability-Lookup</name>
    <email>csirt@opendfir.org</email>
  </author>
  <link href="https://cve.radiocsirt.org" rel="alternate"/>
  <generator uri="https://lkiesow.github.io/python-feedgen" version="1.0.0">python-feedgen</generator>
  <subtitle>Contains only the most 10 recent entries.</subtitle>
  <entry>
    <id>https://cve.radiocsirt.org/vuln/cve-2021-32986</id>
    <title>CVE-2021-32986 — Automation Direct CLICK PLC CPU Modules Authentication Bypass Using an Alternate Path or Channel</title>
    <updated>2026-10-07T21:02:11.201286+00:00</updated>
    <content type="xhtml">
      <div xmlns="http://www.w3.org/1999/xhtml"><p><strong>Affected:</strong> Automation Direct CLICK PLC CPU Modules: C0-1x CPUs</p>
<p>After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.</p></div>
    </content>
    <link href="https://cve.radiocsirt.org/vuln/cve-2021-32986"/>
  </entry>
</feed>