    <id>https://cve.radiocsirt.org/vuln/certfr-2016-avi-178</id>
    <title>certfr-2016-avi-178 — De multiples vulnérabilités ont été corrigées dans &lt;span
class="textit"&gt;SCADA Siemens SIPROTEC 4 et SIPROTEC Compact&lt;/s…</title>
    <updated>2026-10-21T10:59:34.928309+00:00</updated>
    <content>certfr-2016-avi-178</content>
    <link href="https://cve.radiocsirt.org/vuln/certfr-2016-avi-178"/>
  </entry>
  <entry>
    <id>https://cve.radiocsirt.org/vuln/cnvd-2016-03387</id>
    <title>cnvd-2016-03387</title>
    <updated>2026-10-21T10:59:34.928347+00:00</updated>
    <content>cnvd-2016-03387</content>
    <link href="https://cve.radiocsirt.org/vuln/cnvd-2016-03387"/>
  </entry>
  <entry>
    <id>https://cve.radiocsirt.org/vuln/euvd-2026-184882</id>
    <title>EUVD-2026-184882</title>
    <updated>2026-10-21T10:59:34.928361+00:00</updated>
    <content>EUVD-2026-184882</content>
    <link href="https://cve.radiocsirt.org/vuln/euvd-2026-184882"/>
  </entry>
  <entry>
    <id>https://cve.radiocsirt.org/vuln/fkie_cve-2016-4784</id>
    <title>fkie_cve-2016-4784</title>
    <updated>2026-10-21T10:59:34.928381+00:00</updated>
    <content type="xhtml">
      <div xmlns="http://www.w3.org/1999/xhtml">
        <p>A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions &lt; V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions &lt; V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions &lt; V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions &lt; V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions &lt; 1.02.02; SIPROTEC 7SJ686 : All versions &lt; V 4.83; SIPROTEC 7UT686 : All versions &lt; V 4.01; SIPROTEC 7SD686 : All versions &lt; V 4.03; SIPROTEC 7SJ66 : All versions &lt; V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained.</p>
      </div>
    </content>
    <link href="https://cve.radiocsirt.org/vuln/fkie_cve-2016-4784"/>
  </entry>
  <entry>
    <id>https://cve.radiocsirt.org/vuln/ghsa-388g-95vj-q36x</id>
    <title>GHSA-388g-95vj-q36x</title>
    <updated>2026-10-21T10:59:34.928413+00:00</updated>
    <content type="xhtml">
      <div xmlns="http://www.w3.org/1999/xhtml">
        <p>A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions &lt; V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions &lt; V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions &lt; V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions &lt; V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions &lt; 1.02.02; SIPROTEC 7SJ686 : All versions &lt; V 4.83; SIPROTEC 7UT686 : All versions &lt; V 4.01; SIPROTEC 7SD686 : All versions &lt; V 4.03; SIPROTEC 7SJ66 : All versions &lt; V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained.</p>
      </div>
    </content>
    <link href="https://cve.radiocsirt.org/vuln/ghsa-388g-95vj-q36x"/>
  </entry>
  <entry>
    <id>https://cve.radiocsirt.org/vuln/gsd-2016-4784</id>
    <title>gsd-2016-4784</title>
    <updated>2026-10-21T10:59:34.928433+00:00</updated>
    <content>gsd-2016-4784</content>
    <link href="https://cve.radiocsirt.org/vuln/gsd-2016-4784"/>
  </entry>
  <entry>
    <id>https://cve.radiocsirt.org/vuln/icsa-16-140-02</id>
    <title>ICSA-16-140-02 — Siemens SIPROTEC Information Disclosure Vulnerabilities (Update B)</title>
    <updated>2026-10-21T10:59:34.928444+00:00</updated>
    <content type="xhtml">
      <div xmlns="http://www.w3.org/1999/xhtml">
        <p>A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions &lt; V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions &lt; V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions &lt; V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions &lt; V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions &lt; 1.02.02; SIPROTEC 7SJ686 : All versions &lt; V 4.83; SIPROTEC 7UT686 : All versions &lt; V 4.01; SIPROTEC 7SD686 : All versions &lt; V 4.03; SIPROTEC 7SJ66 : All versions &lt; V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained. A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions &lt; V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions &lt; V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions &lt; V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions &lt; V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions &lt; 1.02.02. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain a limited amount of device memory content if network access was obtained. This vulnerability only affects EN100 Ethernet module included in SIPROTEC4 and SIPROTEC Compact devices.</p>